The AC690 is designed to meet the requirements of all variable speed drive applications up to 1500HP, from simple single motor speed control through to the most sophisticated integrated multi-drive systems
Features:
The AC690 can be user configured for 3 different modes of operation :
• Open-loop (volts/frequency) control
This mode is ideal for basic motor speed control, or multiple motors driven in parallel. The quick set-up menu and plain language display ensures the quickest and easiest, trouble free start up.
• Sensorless vector control
High starting torque and tight speed regulation is provided by a sophisticated MRAS (Model Reference Adaptive System) motor control strategy. MRAS provides accurate speed simulation (without the need for any speed measuring transducer) by continually modeling the motor.
• Closed-loop vector control
Full closed-loop flux vector performance can be achieved with the AC690+ by simply adding an encoder feedback ‘technology box’. This provides 100% continuous full load standstill torque plus a highly dynamic speed loop (up to 45 Hz bandwidth) ; more than sufficient for the most demanding of applications.
Advantages:
• Pre-programmed application macros
• Open standard fieldbus communications
• Programming identical to DC 590+ DC drives
• Mechanical protection options to suit all environments : IP 20 – IP40/NEMA 1 – IP54 – Through panel mounting
• Class B EMC filters
• Energy Saving (fast return on investment in pump and fan applications)
• Line regenerative AFE units available
• HVAC series available with line bypass
Standards:
The AC690+ series meets the following standards when installed in accordance with the relevant product manual:
• CE Marked to EN50178 (Safety, Low Voltage Directive)
• CE Marked to EN61800-3 (EMC Directive)
• UL listed to US Standard UL508C
• cUL listed to Canadian Standard C22.2 #14
Technical Specifications:
Power Supply:
Single Phase Units
– 220-240VAC +/- 10 %, 50-60 Hz +/- 5% (1 to 3HP)
Three Phase Units
– 220-240VAC +/- 10 %, 50-60 Hz +/- 5% (1 to 75HP)
– 380-460VAC +/- 10 %, 50-60 Hz +/- 5% (1 to 1500HP)
Environment:
0-45°C (Constant torque / 40°C with IP40 cover / derate to 50°C)
Up to 1000m ASL (derate 1% per 100m above 1000m)
Protection:
IP 20 – IP40/NEMA 1 – IP54
Overload:
Constant torque rating : 150% for 60 seconds, 180% for 1 second
Variable torque rating (pumps and fans) : 115% for 10 seconds
Output Frequency:
Volts/Hertz mode: 0-590Hz
Sensorless vector mode: 0-120Hz
Closed loop vector mode: 0-300Hz
Switching Frequency:
Frame B = 3, 6 or 9kHz / Frame C, D, E and F = 3 or 6kHz – All with audibly silent switching frequency.
Dynamic Braking:
Each drive can be fitted with an internal dynamic brake switch
(Frame B and C : standard / Frame D, E and F : optional)
Analog Inputs:
4 Configurable, 10bits (13 bits with optional system card) / 0-10V, 0-±10V, 0-20mA, 4-20mA
Analog Outputs:
3 Configurable, 10 bits / 0-10V, 0-±10V, 0-20mA, 4-20mA
Digital Inputs:
7 Configurable, nominal 24Vdc (30V dc max)
Digital Outputs:
3 Configurable, relay contacts 3A/230 Vac
Reference Supplies:
+10Vdc, -10Vdc, +24Vdc
Motor Thermistor Input
Systems Expansion Module:
The optional systems expansion module allows for advanced applications such as phase locking
between drives and register control. Key features include :
• 5 additional user configurable Inputs / Outputs
• 4 high resolution analogue inputs (12 bits plus sign)
• 2 additional encoder inputs
• 2 high speed register mark inputs
• Encoder slave repeater
Performance Characteristics | |
---|---|
Output Rating (HP) | 1 – 1500HP |
Input Voltage | 1*230VAC | 3*230VAC | 3*380-480VAC | 3*500VAC |
Operating Control Modes | V/Hz | Sensorless Vector | Closed Loop Vector |
Communication Interfaces | RS232 / RS485 | CANopen | ControlNet | DeviceNet | Profibus | Ethernet TCP / IP | Johnson Metasys | Link Communications | Modbus | Siemens Apogee | LonWorks |
Certifications | CE (EMC & LVD) | UL Listed | cUL Listed |
Operating Temperature (C) | 0-45C / 0-40C with IP40 cover (derate up to 50C max) |
Operating Temperature (F) | 32-113F / 32-104F with IP40 cover (derate up to 122F max) |
Operating Altitude | Up to 1000m ASL (derate > 1000m) |
Overload Ratings | Heavy Duty Rating (Constant Torque) : 150% for 60s | Heavy Duty Rating (Constant Torque) : 180% for 1s | Normal Duty Rating (Variable Torque – pumps and fans) : 115% for 10s |